NYM-J Installation Cable 3×1.5mm²
General purpose PVC-insulated installation cable for fixed wiring in dry, damp and wet locations. Ideal for domestic and light commercial installations. Grey outer sheath with colour-coded conductors (brown, blue, green/yellow).
| Conductor cross-section | 3 × 1.5 mm² |
| Conductor material | Solid copper (Class 1) |
| Insulation | PVC (grey outer sheath) |
| Rated voltage | 300/500V |
| Max. operating temp. | +70°C (conductor) |
| Min. install temp. | −5°C |
| Flame retardant | IEC 60332-1 |
| Standard | DIN VDE 0250 / IEC 60228 |
| Available lengths | 50m, 100m, 500m drums |
| Outer diameter | approx. 9.2 mm |
H07V-K Single Core Flexible Cable 1×2.5mm²
Flexible PVC-insulated single conductor cable for switchboard and panel wiring. Finely stranded copper conductor for ease of termination in tight spaces. Available in full colour range.
| Conductor cross-section | 1 × 2.5 mm² |
| Conductor material | Fine stranded copper (Class 5) |
| Insulation | PVC |
| Rated voltage | 450/750V |
| Max. operating temp. | +70°C |
| Conductor resistance | ≤7.41 Ω/km at 20°C |
| Standard | IEC 60227-3 / EN 50525-2-31 |
| Colours available | Brown, Blue, Black, Grey, Red, Yellow, Green/Yellow |
| Available lengths | 100m spools |
| Outer diameter | approx. 4.1 mm |
NYY-J Power Cable 4×16mm²
Heavy-duty PVC power cable for direct burial and underground installation. Four-core construction for three-phase + neutral circuits in industrial and infrastructure applications. Black outer sheath, UV resistant.
| Conductor cross-section | 4 × 16 mm² |
| Conductor material | Stranded copper (Class 2) |
| Insulation | PVC inner / PVC outer sheath (black) |
| Rated voltage | 0.6/1kV |
| Max. operating temp. | +90°C (short circuit) |
| Min. bending radius | 6× outer diameter |
| Current rating | 69A (direct buried) |
| Standard | DIN VDE 0276 / IEC 60502-1 |
| Available lengths | 50m, 100m drums |
| Outer diameter | approx. 24.5 mm |
SWA Armoured Cable 3×2.5mm² Steel Wire
Steel wire armoured power cable for applications requiring mechanical protection. Suitable for outdoor, underground and industrial environments. LSF (Low Smoke & Fume) option available.
| Conductor cross-section | 3 × 2.5 mm² |
| Conductor material | Stranded copper (Class 2) |
| Insulation | XLPE inner / PVC bedding / SWA / PVC outer |
| Rated voltage | 600/1000V |
| Armouring | Galvanised steel wire |
| Max. operating temp. | +90°C |
| Current rating | 31A (clipped direct) |
| Standard | BS 5467 / IEC 60502-1 |
| Available lengths | 50m, 100m drums |
| Outer diameter | approx. 16.4 mm |
Silicone Heat-Resistant Cable 2×1.5mm² 180°C
High-temperature silicone insulated cable for sauna heaters, ovens, industrial furnaces and proximity heating applications. Exceptional flexibility maintained at low temperatures. Halogen-free.
| Conductor cross-section | 2 × 1.5 mm² |
| Conductor material | Fine stranded tinned copper |
| Insulation | Silicone rubber (SiR) |
| Rated voltage | 300/500V |
| Max. operating temp. | +180°C continuous |
| Min. install temp. | −60°C |
| Halogen-free | Yes |
| Standard | IEC 60245-4 / EN 50525-2-21 |
| Available lengths | 100m spools |
| Outer diameter | approx. 8.0 mm |
Double Pole Isolator Switch 20A 250V AC
Surface-mount double pole switch-disconnector for isolation of single-phase circuits. Positive break mechanism ensures full isolation. Suitable for isolation of boilers, water heaters and A/C units. IP20 rating, DIN rail or surface mount.
| Rated current | 20A |
| Rated voltage | 250V AC |
| Poles | 2 (Double Pole) |
| Switching type | Positive break / switch-disconnector |
| Protection rating | IP20 |
| Mounting | Surface or DIN rail |
| Operating temp. | −25°C to +55°C |
| Terminal capacity | Up to 16mm² |
| Standard | IEC 60669-1 / EN 60947-3 |
| Colour | White RAL 9010 |
Wall Switch 10AX 2-Way Single Gang
Slim-profile flush-mount 2-way rocker switch for domestic and light commercial lighting circuits. Smooth rocker action, screwless terminal connections, and deep back box compatibility. Part of a full modular accessories range.
| Rated current | 10AX (resistive) |
| Rated voltage | 250V AC |
| Switching | 2-way (1-way configurable) |
| Gang | 1-gang |
| Mounting | Flush (25mm back box) |
| Fixings | 35mm standard centres |
| Terminal type | Screwless push-in or screw |
| Protection rating | IP2X (front) |
| Standard | IEC 60669-1 |
| Colour | White / Brushed Steel / Black options |
Rotary Cam Switch 63A 4-Pole Industrial
Heavy-duty industrial rotary cam switch for three-phase motor and equipment isolation. Spring-return handle mechanism with clearly marked ON/OFF positions. Panel or DIN rail mount. Lockable in OFF position with padlock.
| Rated current | 63A (AC-23A) |
| Rated voltage | 690V AC / 220V DC |
| Poles | 4 |
| Utilisation category | AC-23A (motor loads) |
| Short circuit withstand | 10kA (with 63A fuse) |
| Protection rating | IP65 (front) |
| Padlockable | Yes (OFF position) |
| Terminal capacity | Up to 35mm² |
| Standard | IEC 60947-3 / EN 60947-3 |
| Operating temp. | −25°C to +55°C |
Socket Outlet 16A 2P+E Schuko Surface Mount
Standard Schuko (CEE 7/4) surface-mount socket outlet with earth contact. Safety shutters on all poles prevent accidental contact. Robust polycarbonate housing rated for continuous 16A loads. Suitable for indoor and protected outdoor use.
| Rated current | 16A |
| Rated voltage | 250V AC |
| Poles | 2P+E (Schuko CEE 7/4) |
| Mounting | Surface (35mm back box) |
| Safety shutters | Yes (all poles) |
| Protection rating | IP44 |
| Housing material | Polycarbonate (PC) |
| Terminal capacity | Up to 4mm² |
| Standard | IEC 60884-1 / CEE 7/4 |
| Colour | White |
18-Way Split Load Consumer Unit with RCD
18th Edition compliant split-load consumer unit with dual RCD protection. Suitable for new installations and upgrades. Metal enclosure, 100A main switch, two 63A/30mA RCDs protecting separate circuits. Pre-wired busbar, all terminals clearly labelled.
| Number of ways | 18 (split 9+9) |
| Main switch | 100A double pole isolator |
| RCD protection | 2× 63A/30mA (Type AC) |
| Busbar rating | 100A |
| Enclosure material | Steel (RAL 9016 white) |
| Protection rating | IP2XC (door closed) |
| MCB capacity | 18 × Type B/C (up to 32A each) |
| Fault level | 10kA |
| Standard | IEC 61439-3 / BS EN 61439-3 |
| Dimensions | 397 × 236 × 104mm |
IP65 Weatherproof Enclosure 300×200×150mm
Polycarbonate IP65 rated enclosure for outdoor and wet area installations. UV-stabilised grey housing with stainless steel lid screws. Transparent lid version available. Pre-punched knockouts on all sides. Suitable for pump control panels, irrigation and outdoor distribution.
| Dimensions (H×W×D) | 300 × 200 × 150 mm |
| Protection rating | IP65 / IK08 |
| Material | UV-stabilised polycarbonate (PC) |
| Lid fixings | 4× M4 stainless steel screws |
| Lid options | Opaque or transparent |
| Knockouts | Pre-punched sides & base |
| DIN rail | Optional (35mm, mountable inside) |
| Temp. range | −40°C to +70°C |
| Standard | IEC 60670 / EN 60670 |
| Colour | Grey RAL 7035 |
12-Way Flush Mount Distribution Board
Flush mounted steel distribution board for domestic and light commercial applications. Accepts standard 17.5mm DIN rail MCBs. Includes blanking plates for unused ways. Pre-drilled for wall fixings, integrated earth/neutral bars, cable entry from top or bottom.
| Number of ways | 12 |
| Busbar rating | 63A |
| Enclosure material | Powder-coated steel |
| Mounting | Flush (recessed in wall) |
| DIN rail | 35mm (EN 50022) |
| Neutral/Earth bars | Included (12-way each) |
| Cable entry | Top and bottom |
| Protection rating | IP40 |
| Standard | IEC 61439-3 |
| Dimensions | 270 × 210 × 85mm |
PVC Cable Management Trunking 60×40mm (2m)
White PVC cable management trunking for concealed surface cable runs in commercial and domestic environments. Snap-on lid for fast installation. Full range of accessories available: corners, tees, end caps, junctions. 2-metre lengths.
| Dimensions (W×D) | 60 × 40 mm |
| Length per piece | 2000 mm |
| Material | PVC (self-extinguishing) |
| Lid type | Snap-on (tool-free removal) |
| Flame retardant | V0 (UL 94) |
| Max. cable fill | 60% (approx. 18× 2.5mm² cables) |
| Operating temp. | −5°C to +60°C |
| Colour | White RAL 9010 |
| Standard | IEC 61084-1 / EN 61084-1 |
| Pack quantity | 10 pieces per box (20m) |
Rotary Leading Edge Dimmer 400W
Traditional leading-edge rotary dimmer for incandescent and halogen loads. Push on/off with rotary level control. Maintains last-set dim level on switch-on. Integral overload and overtemperature protection. Flush mount, compatible with standard back boxes.
| Max. load | 400W |
| Min. load | 40W |
| Dimming type | Leading edge (TRIAC) |
| Compatible loads | Incandescent, Halogen (mains voltage) |
| Rated voltage | 230V AC 50Hz |
| Control type | Rotary knob with push on/off |
| Memory function | Yes (retains dim level) |
| Mounting | Flush (35mm centres) |
| Protection | Overload + overtemperature |
| Standard | EN 60669-2-1 |
Universal LED Dimmer 200W Trailing Edge
Multi-way compatible trailing edge dimmer engineered for LED and CFL loads. Auto-detects load type for optimal dimming performance. Adjustable minimum and maximum dim level via trim controls. Works with most branded LED lamps. Includes temperature sensor cutout.
| Max. load | 200W (LED) / 400W (incandescent) |
| Min. load | 10W (LED) |
| Dimming type | Trailing edge (MOSFET) |
| Compatible loads | LED, CFL, Incandescent, Low-voltage Halogen |
| Rated voltage | 230V AC 50Hz |
| Auto detection | Yes |
| Multi-way | Up to 10 way (with remote plates) |
| Adjustable trim | Min + Max via screwdriver |
| Mounting | Flush (35mm centres) |
| Standard | EN 60669-2-1 / EMC Directive |
Smart Wireless Dimmer 250W Zigbee
Zigbee 3.0 smart dimmer integrating with major home automation platforms including Home Assistant, Amazon Alexa, Google Home and Apple HomeKit (via hub). Physical push/slide control retained for normal operation. OTA firmware updates. No neutral wire required on most installations.
| Max. load | 250W (LED) / 500W (incandescent) |
| Wireless protocol | Zigbee 3.0 (2.4GHz) |
| Compatible platforms | Home Assistant, Alexa, Google Home, Apple HomeKit (via hub) |
| Dimming type | Trailing edge (MOSFET) |
| Rated voltage | 230V AC 50Hz |
| Neutral required | No (most circuits) |
| Physical control | Yes (push on/off + slide dimmer) |
| OTA updates | Yes |
| Mounting | Flush (35mm centres) |
| Certifications | CE, RED, RoHS |
Motor Speed Controller 5A Ventilation Fan
Dedicated speed controller for single-phase induction motors and ventilation fans. Stepless speed control from approximately 20% to 100%. Built-in motor protection (locked rotor protection). Suitable for duct fans, ceiling fans and bathroom extractors.
| Max. load | 5A / 1150W |
| Load type | Single-phase induction motor |
| Control type | TRIAC (stepless) |
| Speed range | ~20–100% of rated speed |
| Rated voltage | 230V AC 50Hz |
| Motor protection | Locked rotor protection |
| Control interface | Rotary knob |
| Mounting | Flush (35mm centres) |
| Applications | Duct fans, ceiling fans, extractors |
| Standard | EN 60669-2-1 |
MCB 10A Type B Single Pole 6kA
Type B miniature circuit breaker for residential and light commercial applications. Suitable for lighting, socket and general purpose circuits. DIN rail mount (35mm), snap-on. Toggle handle with ON/OFF/TRIPPED positions clearly visible. Rated for 10,000 operations at full load.
| Rated current | 10A |
| Trip characteristic | Type B (3–5× In) |
| Poles | 1 (Single Pole) |
| Rated voltage | 230/400V AC |
| Breaking capacity | 6kA (EN 60898) |
| DIN rail | 35mm (1 module = 17.5mm) |
| Terminal capacity | 1–25mm² |
| Operating temp. | −25°C to +70°C |
| Mechanical life | 10,000 operations |
| Standard | IEC/EN 60898-1 |
RCD 40A 30mA Type AC Double Pole
Type AC residual current device providing personal protection against earth leakage faults. 30mA sensitivity provides shock protection. 40A rating suitable as main RCD in consumer units. Includes test button for periodic functional testing. 2-module DIN rail width.
| Rated current | 40A |
| Rated sensitivity | 30mA |
| RCD type | Type AC |
| Poles | 2 (Double Pole) |
| Rated voltage | 230V AC 50Hz |
| Break time | <30ms at In∆ |
| DIN rail | 35mm (2 modules = 35mm) |
| Terminal capacity | 1–35mm² |
| Test button | Yes |
| Standard | IEC/EN 61008-1 |
RCBO 16A Type C 30mA Single Pole
Combined residual current circuit breaker with overcurrent protection — RCBO. Provides both earth leakage (RCD) and overcurrent (MCB Type C) protection in a single 1-module DIN rail device. Ideal for final circuits requiring individual RCD protection without a split-load board.
| Rated current | 16A |
| Trip characteristic | Type C (5–10× In) |
| RCD sensitivity | 30mA Type A |
| Poles | 1+N (Single Pole) |
| Rated voltage | 230V AC 50Hz |
| Breaking capacity | 6kA |
| DIN rail | 35mm (1 module = 17.5mm) |
| Terminal capacity | 1–25mm² |
| Test button | Yes |
| Standard | IEC/EN 61009-1 |
Surge Protection Device Type 2 — 40kA
Type 2 (Class II) surge protection device for protection of electrical installations against transient overvoltages caused by lightning and switching surges. DIN rail mount, visual indication of protection status, replaceable protection modules. 3+N or 1+N configurations available.
| SPD Type | Type 2 (Class II) |
| Discharge current (Imax) | 40kA (8/20µs per pole) |
| Nominal discharge current (In) | 20kA |
| Voltage protection level (Up) | ≤1.5kV |
| Max. continuous voltage (Uc) | 275V AC |
| Configuration | 1+N (single phase) / 3+N (three phase) |
| Status indication | Visual (window) + remote signalling option |
| Replaceable modules | Yes |
| DIN rail | 35mm |
| Standard | IEC 61643-11 / EN 61643-11 |